SIZE RANGE | 50 – 1,200 HP |
EMISSIONS | Uncontrolled |
TURNDOWN | Up to 8:1 |
FUELS | NG, LPG, Biogas or Dual-Fuel (#2-6 Oil) |
FD68 burners feature a highly engineered damper with a triple-disc or inlet vane design. This helps to maintain optimum combustion throughout the firing range.
MODEL: | 50 | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 625 | 800 | 1000 | 1200 | |
Boiler Output | HP | 50 | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 625 | 800 | 1000 | 1200 |
Gas Capacity | MBH | 2100 | 3150 | 4200 | 5250 | 6300 | 8400 | 10500 | 12600 | 16800 | 21000 | 26250 | 33600 | 42000 | 50400 |
Blower Motor | HP | 1/2 | 3/4 | 1.5 | 2 | 2 | 5 | 7.5 | 7.5 | 15 | 20 | 25 | 30 | 40 | 75 |
Min Gas Pressure | PSI | 0.5 | 0.5 | 0.5 | 0.5 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.5 | 2 | 2 | 2 | 2 |
Furnace Pressure | IN W.C. | 0.75 | 0.75 | 1 | 1 | 1.5 | 2 | 2 | 3 | 4 | 4 | 4 | 4 | 4 | 4 |
Shipping Weight | LBS | 1000 | 1000 | 1000 | 1000 | 1250 | 1250 | 1250 | 1700 | 1700 | 1800 | 1800 | 2500 | 2500 | 3000 |
A1 | IN | 36.3 | 36.3 | 36.3 | 36.3 | 44.5 | 44.5 | 44.5 | 53 | 53 | 57.6 | 57.6 | 67 | 67 | 78.5 |
A2 | IN | 41.2 | 41.2 | 41.2 | 41.2 | 50.7 | 50.7 | 50.7 | 61.4 | 61.4 | 69.5 | 69.5 | 80.5 | 80.5 | 92.5 |
B | IN | 21.25 | 21.25 | 21.25 | 21.25 | 25.25 | 25.25 | 25.25 | 30.25 | 30.25 | 35.25 | 35.25 | 39.5 | 39.5 | 39.5 |
C | IN | 22.5 | 22.5 | 22.5 | 22.5 | 26.5 | 26.5 | 26.5 | 31.5 | 31.5 | 36.5 | 36.5 | 41 | 41 | 41 |
D | IN | 16 | 16 | 16 | 16 | 19.125 | 19.125 | 19.125 | 20 | 22 | 22.75 | 23.75 | 28 | 28 | 32 |
E1 | IN | 15.7 | 15.7 | 15.7 | 15.7 | 17.9 | 17.9 | 17.9 | 20.5 | 20.5 | 23.2 | 23.2 | 25.2 | 25.2 | 25.2 |
E2 | IN | 22.3 | 22.3 | 22.3 | 22.3 | 24.5 | 24.5 | 24.5 | 27.1 | 27.1 | 29.8 | 29.8 | 31.8 | 31.8 | 31.8 |